Sidebar
			
		
		 
				
						
        	
						
				
						 
				
														
					
									
				 	
				
						
					
												
				
				
					
			
						
		
						
			
		
				
			
										
		    
				
																									 					
					
						
																						
							
							
								
									
									
						            
										
	
	
	
										
																		
																	
								
					            					            
						            
					            
					            
					            
																
																
							
						
					
				
				
								
				
			
						
		
    
              Schneider VW3A5218 Sinus filter - 75 A - for Altivar Process variable speed drives
						Viewed  1143 times
					
										
				Product Description
Schneider VW3A5218 Sinus filter - 75 A - for Altivar Process variable speed drives
| product or component type | 
				Sinus filter | |
|---|---|---|
| range compatibility | 
				Altivar Process ATV600 Altivar Process ATV900 | |
| product specific application | 
				Output filter | |
| [In] rated current | 
				75 A | |
| thermal losses | 
				500 W, 115 °C | |
| product compatibility | 
				ATV630 variable speed drive wall mount - 45 kW, 500...690 V 
				three phase ATV630 variable speed drive wall mount - 55 kW, 500...690 V three phase ATV930 variable speed drive wall mount - 45 kW, 500...690 V three phase ATV930 variable speed drive wall mount - 55 kW, 500...690 V three phase ATV630 variable speed drive wall mount, 60 hp, 600 V three phase ATV630 variable speed drive wall mount, 75 hp, 600 V three phase ATV930 variable speed drive wall mount, 60 hp, 600 V three phase ATV930 variable speed drive wall mount, 75 hp, 600 V three phase | |
| switching frequency | 
				2 kHz | |
| output frequency | 
				70 Hz | |
| maximum permissible voltage | 
				690 V AC | 
| electrical connection | 
				Terminal | |
|---|---|---|
| max current | 
				1.5 x nominal current for 60 s | |
| product weight | 
				75 kg | 
| IP degree of protection | 
				IP00 | |
|---|---|---|
| pollution degree | 
				2 conforming to EN 50178 | |
| vibration resistance | 
				1 gn (f = 13...200 Hz) conforming to IEC 60068-2 1.5 mm peak to peak (f = 3...13 Hz) conforming to IEC 60068-2 | |
| shock resistance | 
				15 gn for 11 ms conforming to IEC 60068-2-27 | |
| relative humidity | 
				0...95 % | |
| ambient air temperature for operation | 
				-10...45 °C | |
| ambient air temperature for storage | 
				-40...65 °C | |
| operating altitude | 
				<= 1000 m without current derating 1000...3000 m with current derating 1 % per 100 m | |
| standards | 
				UL 508 | 