Sidebar
Schneider TMC2AI2 Cartridge M221 - 2 analog inputs - I/O extension
Viewed 1180 times
Product Description
Schneider TMC2AI2 Cartridge M221 - 2 analog inputs - I/O extension
| range of product |
Modicon M221
|
|
|---|---|---|
| product or component type |
Analogue input cartridge
|
|
| product compatibility |
Modicon M221C
|
|
| analogue input number |
2
|
| analogue input type |
Current, input range: 4...20 mA
Current, input range: 0...20 mA Voltage, input range: 0...10 V |
|
|---|---|---|
| analogue input resolution |
12 bits
|
|
| LSB value |
3.91 µA (current), input range: 4...20 mA
2.44 mV (voltage), input range: 0...10 V 4.88 µA (current), input range: 0...20 mA |
|
| conversion time |
20 ms
|
|
| sampling duration |
10 ms
|
|
| absolute accuracy error |
+/- 1 % of full scale
+/- 0.1 % of full scale 25 °C |
|
| temperature drift |
+/- 0.02 %FS/°C
|
|
| repeat accuracy |
+/- 0.5 %FS
|
|
| non-linearity |
+/- 0.01 %FS
|
|
| cross talk |
<= 1 LSB
|
|
| type of cable |
Twisted shielded pairs cable
|
|
| electrical connection |
2 screw terminal blocks (pitch 3.81 mm) 1.5 mm² 3 for inputs
|
|
| cable distance between devices |
Twisted shielded pairs cable: 30 m for input
|
|
| insulation |
Non-insulated between analogue input and internal logic
|
|
| height |
41 mm
|
|
| depth |
15 mm
|
|
| width |
35 mm
|
|
| product weight |
0.015 kg
|
|
| permissible continuous overload |
13 V (voltage)
40 mA (current) |
|
| input impedance |
<= 250 Ohm current
>= 1 MOhm voltage |
| immunity to microbreaks |
10 ms
|
|---|