Sidebar
			
		
		 
				
						
        	
						
				
						 
				
														
					
									
				 	
				
						
					
												
				
				
					
			
						
		
						
			
		
				
			
										
		    
				
																									 					
					
						
																						
							
							
								
									
									
						            
										
	
	
	
										
																		
																	
								
					            					            
						            
					            
					            
					            
																
																
							
						
					
				
				
								
				
			
						
		
    
              Schneider TMC2TI2 Cartridge M221 - 2 temperature inputs - I/O extension
						Viewed  1041 times
					
										
				Product Description
Schneider TMC2TI2 Cartridge M221 - 2 temperature inputs - I/O extension
| range of product | 
			 
				Modicon M221 
			 | 
			|
|---|---|---|
| product or component type | 
			 
				Analogue input cartridge 
			 | 
			|
| product compatibility | 
			 
				Modicon M221C 
			 | 
			|
| analogue input number | 
			 
				2 
			 | 
			
| analogue input type | 
			 
				Thermocouple, input range: - 200...1000 °C for thermocouple J 
			Thermocouple, input range: - 200...1300 °C for thermocouple K Thermocouple, input range: 0...1760 °C for thermocouple R Thermocouple, input range: 0...1760 °C for thermocouple S Thermocouple, input range: 0...1820 °C for thermocouple B Thermocouple, input range: - 200...400 °C for thermocouple T Thermocouple, input range: - 200...1300 °C for thermocouple N Thermocouple, input range: - 200...800 °C for thermocouple E Thermocouple, input range: 0...2315 °C for thermocouple C Temperature probe, input range: - 60...180 °C (Ni 100/Ni 1000) Temperature probe, input range: - 200...850 °C (Pt 100) Temperature probe, input range: - 200...600 °C (Pt 1000)  | 
			|
|---|---|---|
| analogue input resolution | 
			 
				14 bits 
			 | 
			|
| LSB value | 
			 
				0.1 °C 
			 | 
			|
| sampling duration | 
			 
				125 ms (thermocouple) 
			250 ms (temperature probe)  | 
			|
| absolute accuracy error | 
			 
				+/- 0.1 % of full scale Pt 100/Pt 1000, Ni 100/ Ni 1000 25 °C 
			+/- 0.4 % of full scale thermocouple K - 200...0 °C 25 °C +/- 0.1 % of full scale thermocouple K 0...1300 °C 25 °C +/- 0.4 % of full scale thermocouple J - 200...0 °C 25 °C +/- 0.1 % of full scale thermocouple J 0...1000 °C 25 °C +/- 0.4 % of full scale thermocouple E - 200...0 °C 25 °C +/- 0.1 % of full scale thermocouple E 0...800 °C 25 °C +/- 0.4 % of full scale thermocouple T - 200...0 °C 25 °C +/- 0.1 % of full scale thermocouple T 0...400 °C 25 °C +/- 0.4 % of full scale thermocouple N - 200...0 °C 25 °C +/- 0.1 % of full scale thermocouple N 0...1300 °C 25 °C +/- 6 °C thermocouple R, S 0...200 °C 25 °C +/- 0.1 % of full scale thermocouple R, S 200...1760 °C 25 °C +/- 0.1 % of full scale thermocouple C 0...2315 °C 25 °C  | 
			|
| temperature drift | 
			 
				+/- 0.02 %FS/°C 
			 | 
			|
| repeat accuracy | 
			 
				+/- 0.5 %FS 
			 | 
			|
| non-linearity | 
			 
				+/- 0.01 %FS 
			 | 
			|
| cross talk | 
			 
				<= 1 LSB 
			 | 
			|
| type of cable | 
			 
				Twisted shielded pairs cable 
			 | 
			|
| electrical connection | 
			 
				2 screw terminal blocks (pitch 3.81 mm) 1.5 mm² 3 for inputs 
			 | 
			|
| cable distance between devices | 
			 
				Twisted shielded pairs cable: 30 m for input 
			 | 
			|
| insulation | 
			 
				Non-insulated between analogue input and internal logic 
			 | 
			|
| height | 
			 
				41 mm 
			 | 
			|
| depth | 
			 
				15 mm 
			 | 
			|
| width | 
			 
				35 mm 
			 | 
			|
| product weight | 
			 
				0.015 kg 
			 | 
			|
| input impedance | 
			 
				>= 1 MOhm 
			 | 
			
| immunity to microbreaks | 
			 
				10 ms 
			 | 
		
|---|