Sidebar
			
		
		 
				
						
        	
						
				
						 
				
														
					
									
				 	
				
						
					
												
				
				
					
			
						
		
						
			
		
				
			
										
		    
				
																									 					
					
						
																						
							
							
								
									
									
						            
										
	
	
	
										
																		
																	
								
					            					            
						            
					            
					            
					            
																
																
							
						
					
				
				
								
				
			
						
		
    
              Schneider TM4PDPS1 Module network TM4 1 Profibus DP slave
						Viewed  1052 times
					
										
				Product Description
Schneider TM4PDPS1 Module network TM4 1 Profibus DP slave
| product or component type | 
			 
				Profibus DP communication module 
			 | 
			
|---|
| range compatibility | 
			 
				Modicon M241 
			Modicon M251  | 
			|
|---|---|---|
| product compatibility | 
			 
				Modicon M241 logic controller 
			Modicon M251 logic controller  | 
			|
| current consumption | 
			 
				290 mA at 5 V DC for communication bus 
			 | 
			|
| power dissipation in W | 
			 
				1.5 W 
			 | 
			|
| integrated connection type | 
			 
				Female SUB-D 9 Profibus DP 
			 | 
			|
| transmission rate | 
			 
				1.5 Mbit/s for bus length of 200 m 
			500 kbit/s for bus length of 400 m 187.5 kbit/s for bus length of 1000 m 9.6...93.75 kbit/s for bus length of 1200 m 3...12 Mbit/s for bus length of 100 m  | 
			|
| communication port protocol | 
			 
				Profibus DP V1 
			Profibus DP V0  | 
			|
| insulation | 
			 
				Between bus and internal logic at 1000 V DC 
			 | 
			|
| local signalling | 
			 
				1 LED green/yellow for power supply 
			1 LED green/red for communication  | 
			|
| electrical connection | 
			 
				Screw connector - terminal for connecting the functional ground 
			SUB-D 9 - 1 female connector for connecting Profibus  | 
			|
| marking | 
			 
				CE 
			 | 
			|
| surge withstand | 
			 
				1 kV (power lines (DC)) with common mode protection conforming 
				to EN/IEC 61000-4-5 
			2 kV (power lines (AC)) with common mode protection conforming to EN/IEC 61000-4-5 2 kV (relay output) with common mode protection conforming to EN/IEC 61000-4-5 1 kV (I/O) with common mode protection conforming to EN/IEC 61000-4-5 1 kV (shielded cable) with common mode protection conforming to EN/IEC 61000-4-5 0.5 kV (power lines (DC)) with differential mode protection conforming to EN/IEC 61000-4-5 1 kV (power lines (AC)) with differential mode protection conforming to EN/IEC 61000-4-5 1 kV (relay output) with differential mode protection conforming to EN/IEC 61000-4-5 0.5 kV (I/O) with differential mode protection conforming to EN/IEC 61000-4-5  | 
			|
| mounting support | 
			 
				Top hat type TH35-15 rail conforming to IEC 60715 
			Top hat type TH35-7.5 rail conforming to IEC 60715 Plate or panel with fixing kit  | 
			|
| width | 
			 
				25 mm 
			 | 
			|
| height | 
			 
				90 mm 
			 | 
			|
| depth | 
			 
				90 mm 
			 | 
			|
| product weight | 
			 
				0.1 kg 
			 | 
			
| standards | 
			 
				UL 508 
			EN/IEC 61131-2 EIA-485  | 
			|
|---|---|---|
| product certifications | 
			 
				C-Tick 
			cULus  | 
			|
| resistance to electrostatic discharge | 
			 
				8 kV (in air) conforming to Marine specification (LR, ABS, DNV, 
				GL) 
			6 kV (on contact) conforming to Marine specification (LR, ABS, DNV, GL) 4 kV (on contact) conforming to EN/IEC 61000-4-2 8 kV (in air) conforming to EN/IEC 61000-4-2  | 
			|
| resistance to electromagnetic fields | 
			 
				10 V/m (80 MHz...1 GHz) conforming to EN/IEC 61000-4-3 
			3 V/m (1.4 GHz...2 GHz) conforming to EN/IEC 61000-4-3 1 V/m (2...2.7 GHz) conforming to EN/IEC 61000-4-3  | 
			|
| resistance to fast transients | 
			 
				2 kV (relay output) conforming to EN/IEC 61000-4-4 
			1.5 kV (I/O) conforming to EN/IEC 61000-4-4 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4 1 kV (serial link) conforming to EN/IEC 61000-4-4 2 kV (power lines) conforming to EN/IEC 61000-4-4  | 
			|
| resistance to conducted disturbances | 
			 
				10 V (0.15...80 MHz) conforming to EN/IEC 61000-4-6 
			3 V (0.1...80 MHz) conforming to Marine specification (LR, ABS, DNV, GL) 10 V (spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz)) conforming to Marine specification (LR, ABS, DNV, GL)  | 
			|
| electromagnetic emission | 
			 
				Conducted emissions - test level: 120...69 dBµV/m QP ( power 
				lines) at 10...150 kHz conforming to EN/IEC 55011 
			Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15...0.5 MHz conforming to EN/IEC 55011 Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5...300 MHz conforming to EN/IEC 55011 Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5...30 MHz conforming to EN/IEC 55011 Radiated emissions - test level: 40 dBμV/m QP class A at 30...230 MHz conforming to EN/IEC 55011 Radiated emissions - test level: 60...54 dBμV/m QP at 30...100 MHz conforming to Marine specification (LR, ABS, DNV, GL) Radiated emissions - test level: 24 dBμV/m QP at 156...165 MHz conforming to Marine specification (LR, ABS, DNV, GL) Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150...1500 kHz conforming to EN/IEC 55011 Radiated emissions - test level: 47 dBμV/m QP class A at 230...1000 MHz conforming to EN/IEC 55011 Radiated emissions - test level: 80...50 dμV/m QP at 150...30000 kHz conforming to Marine specification (LR, ABS, DNV, GL) Radiated emissions - test level: 54 dBμV/m QP at 100...2000 MHz conforming to Marine specification (LR, ABS, DNV, GL)  | 
			|
| ambient air temperature for operation | 
			 
				-10...55 °C horizontal installation 
			-10...50 °C vertical installation  | 
			|
| ambient air temperature for storage | 
			 
				-25...70 °C 
			 | 
			|
| relative humidity | 
			 
				10...95 % without condensation in operation 
			10...95 % without condensation in storage  | 
			|
| IP degree of protection | 
			 
				IP20 with protective cover in place 
			 | 
			|
| pollution degree | 
			 
				2 
			 | 
			|
| operating altitude | 
			 
				0...2000 m 
			 | 
			|
| storage altitude | 
			 
				0...3000 m 
			 | 
			|
| vibration resistance | 
			 
				1 mm at 5...13.2 Hz on symmetrical rail 
			3 gn at 8.7...150 Hz on symmetrical rail 1 mm at 5...13.2 Hz on panel mounting 0.7 gn at 13.2...100 Hz on panel mounting  | 
			|
| shock resistance | 
			 
				15 gn during 11 ms 
			 | 
		