Sidebar
			
		
		 
				
						
        	
						
				
						 
				
														
					
									
				 	
				
						
					
												
				
				
					
			
						
		
						
			
		
				
			
										
		    
				
																									 					
					
						
																						
							
							
								
									
									
						            
										
	
	
	
										
																		
																	
								
					            					            
						            
					            
					            
					            
																
																
							
						
					
				
				
								
				
			
						
		
    
              Schneider TSXPAY262 Preventa safety module - 24 V DC - standard format - < 5 W
						Viewed  1038 times
					
										
				Product Description
Schneider TSXPAY262 Preventa safety module - 24 V DC - standard format - < 5 W
| range of product | 
			 
				Modicon Premium Automation platform 
			 | 
			|
|---|---|---|
| product or component type | 
			 
				Preventa safety module 
			 | 
			
| [Us] rated supply voltage | 
			 
				24 V DC 
			 | 
			|
|---|---|---|
| supply voltage limits | 
			 
				19.2...30 V 
			 | 
			|
| activation threshold | 
			 
				< 20 V 
			 | 
			|
| short-circuit protection | 
			 
				1 A gG external conforming to IEC 947-5-1 on power supply 
			4 A gG external conforming to IEC 947-5-1 on safety relay outputs  | 
			|
| isolation voltage | 
			 
				4000 V III 2 
			 | 
			|
| discrete input number | 
			 
				1 double or single contact selection input conforming to IEC 
				1131 Type 1 
			1 feedback loop input conforming to IEC 1131 Type 1 1 reset PB input conforming to IEC 1131 Type 1 1 reset PB monitoring input conforming to IEC 1131 Type 1 12 emergency stop or limit switch discrete inputs conforming to IEC 1131 Type 1  | 
			|
| discrete input logic | 
			 
				Positive 
			 | 
			|
| inrush current | 
			 
				<= 0.5 A 
			 | 
			|
| isolation between input and earth | 
			 
				500 Vrms 50/60 Hz for 60 s 
			 | 
			|
| power dissipation in W | 
			 
				< 5 W 
			 | 
			|
| safety outputs | 
			 
				2 NO safety relay AGCDO gold plated volt free output 
			 | 
			|
| [Ue] rated operational voltage | 
			 
				17...127 V DC relay output 
			19...250 V AC relay output  | 
			|
| rated power in VA | 
			 
				120 VA 48 V AC-15 inductive 
			280 VA 110 V AC-15 inductive 550 VA 220 V AC-15 inductive 60 VA 24 V AC-15 inductive  | 
			|
| rated power in W | 
			 
				60 W 24 V DC-13 inductive 100 ms 
			 | 
			|
| [Ithe] conventional enclosed thermal current | 
			 
				<= 2.5 A 
			 | 
			|
| minimum output current | 
			 
				>= 30 mA 
			 | 
			|
| response time on output | 
			 
				< 12 ms 
			 | 
			|
| isolation between output and earth | 
			 
				300 V conforming to DIN VDE 0110 part 2 
			1500 Vrms 50/60 Hz for 60 s  | 
			|
| safety acquisition | 
			 
				Monitor external power supply of the module 
			Read enable inputs Read feedback loop Read the safety outputs control Read status of the 24 inputs  | 
			|
| local signalling | 
			 
				28 LEDs diagnostic of safety system 
			 | 
			|
| electrical connection | 
			 
				1 connector removable screw terminal block 6 pins for connecting 
				the safety output 
			1 connector SUB-D 44 pins for connecting the safety system input  | 
			|
| cable cross section | 
			 
				1.5 mm² with cable end safety output circuit 
			0.2...2.5 mm² without cable end safety output circuit  | 
			|
| current consumption | 
			 
				< 150 mA 5 V DC 
			<= 200 mA 24 V DC  | 
			|
| module format | 
			 
				Standard 
			 | 
			|
| product weight | 
			 
				0.43 kg 
			 | 
			
| ambient air temperature for operation | 
			 
				0...40 °C without fan 
			0...60 °C with fan module  | 
			|
|---|---|---|
| ambient air temperature for storage | 
			 
				-25...70 °C 
			 | 
			|
| IP degree of protection | 
			 
				IP20 conforming to IEC 60529 
			 | 
			|
| standards | 
			 
				CSA C22.2 specific requirements (PLC) 
			EN 954 machine safety parts of control systems EN/IEC 60204-1 machine electrical equipment EN/IEC 61131-2 specific requirements (PLC) EN/ISO 12100 machine electrical equipment ISO 13850 emergency stop equipment UL 508 specific requirements (PLC) ISO 13849-1 category 4 machine safety parts of control systems IEC 61508 SIL 3 machine safety parts of control systems  | 
			|
| product certifications | 
			 
				BG 
			CSA UL  | 
		