Sidebar
Schneider TSXDSY16T3 Discrete output module Modicon Premium - 16 O solid state
Viewed 1067 times
Product Description
Schneider TSXDSY16T3 Discrete output module Modicon Premium - 16 O solid state
| range of product |
Modicon Premium Automation platform
|
|
|---|---|---|
| product or component type |
Discrete output module
|
|
| discrete output number |
16
|
|
| discrete output type |
Solid state protected
|
|
| discrete output voltage |
48 V DC positive conforming to EN/IEC 61131-2 38...60 V
|
|
| discrete output current |
0.25 A
|
| current per channel |
<= 0.31 A
|
|
|---|---|---|
| current per module |
<= 4 A
|
|
| leakage current |
< 0.5 mA at state 0
|
|
| [Ures] residual voltage |
< 1.5 V
|
|
| response time |
1.2 ms
|
|
| switching frequency |
0.5/LI² Hz
|
|
| output overvoltage protection |
By transil diode
|
|
| reverse polarity protection |
Reverse mounted diode
|
|
| output overload protection |
Electronic tripping on reactivation
|
|
| short-circuit protection |
Electronic tripping on reactivation
|
|
| preactuator voltage detection threshold |
34 V
|
|
| load impedance |
>= 192 W
|
|
| isalotion resistance |
> 10 MOhm 500 V
|
|
| power dissipation |
(2.4 W + 0.85 W x No of outputs x current per module)
|
|
| marking |
CE
|
|
| electrical connection |
Screw terminal block
|
|
| current consumption |
80 mA 5 V DC
|
|
| module format |
Standard
|
|
| product weight |
0.34 kg
|
| dielectric strength |
1500 V 50/60 Hz 60 s
|
|
|---|---|---|
| standards |
73/23/EEC
89/336/EEC 92/31/EEC 93/68/EEC CSA C22.2 No 142 IEC 61131-2 UL 508 CSA C22.2 No 213 Class I Division 2 Group A CSA C22.2 No 213 Class I Division 2 Group B CSA C22.2 No 213 Class I Division 2 Group C CSA C22.2 No 213 Class I Division 2 Group D |
|
| product certifications |
ABS
BV DNV GL LR RINA RMRS |
|
| ambient air temperature for operation |
0...60 °C
|
|
| ambient air temperature for storage |
-25...70 °C
|
|
| relative humidity |
10...95 % without condensation for operation
5...95 % without condensation for storage |
|
| operating altitude |
0...2000 m
|
|
| protective treatment |
TC
|
|
| IP degree of protection |
IP20
|
|
| pollution degree |
2
|