Sidebar
			
		
		 
				
						
        	
						
				
						 
				
														
					
									
				 	
				
						
					
												
				
				
					
			
						
		
						
			
		
				
			
										
		    
				
																									 					
					
						
																						
							
							
								
									
									
						            
										
	
	
	
										
																		
																	
								
					            					            
						            
					            
					            
					            
																
																
							
						
					
				
				
								
				
			
						
		
    
              Schneider TSXDSY08R5C Discrete output module - 8 relay not protected output - 12..24 V DC - 3 A
						Viewed  1088 times
					
										
				Product Description
Schneider TSXDSY08R5C Discrete output module - 8 relay not protected output - 12..24 V DC - 3 A
| range of product | 
				Modicon Premium Automation platform | |
|---|---|---|
| product or component type | 
				Discrete output module | |
| discrete output number | 
				8 | |
| discrete output type | 
				Relay not protected | |
| discrete output voltage | 
				12...24 V DC conforming to EN/IEC 61131-2 10...34 V 24...240 V AC conforming to EN/IEC 61131-2 20...264 V | 
| [Ith] conventional free air thermal current | 
				3 A | |
|---|---|---|
| response time | 
				< 10 ms deactivation < 8 ms activation | |
| contacts type and composition | 
				1 NO | |
| output overvoltage protection | 
				AC inductive, by RC circuit MOV (ZNO) on each preactuator DC inductive, by discharge diode on each preactuator | |
| output overload protection | 
				1 external fuse per channel or group of channel fast blow | |
| short-circuit protection | 
				1 external fuse per channel or group of channel fast blow | |
| isalotion resistance | 
				> 10 MOhm 500 V | |
| power dissipation | 
				(0.25 W + 0.2 W x No of outputs at state 1) | |
| electrical durability | 
				1000000 cycles DC-12 24 W 24 V resistive 1000000 cycles DC-3 24 W inductive 2000000 cycles DC-3 10 W inductive 300000 cycles DC-12 40 W 24 V resistive 100000 cycles AC-14 220 VA 220 V inductive 100000 cycles AC-15 220 VA 220 V inductive 1000000 cycles AC-12 110 VA 110 V resistive 1000000 cycles AC-12 220 VA 220 V resistive 1000000 cycles AC-12 50 VA 48 V resistive 1000000 cycles AC-14 110 VA 220 V inductive 1000000 cycles AC-15 110 VA 220 V inductive 150000 cycles AC-14 110 VA 110 V inductive 150000 cycles AC-15 110 VA 110 V inductive 1500000 cycles AC-14 50 VA 110 V inductive 1500000 cycles AC-15 50 VA 110 V inductive 2000000 cycles AC-14 24 VA 48 V inductive 2000000 cycles AC-15 24 VA 48 V inductive 3000000 cycles AC-14 50 VA 220 V inductive 3000000 cycles AC-15 50 VA 220 V inductive 500000 cycles AC-12 110 VA 48 V resistive 500000 cycles AC-12 220 VA 110 V resistive 500000 cycles AC-14 24 VA 24 V inductive 500000 cycles AC-15 24 VA 24 V inductive 5000000 cycles AC-14 10 VA 110 V inductive 5000000 cycles AC-14 10 VA 220 V inductive 5000000 cycles AC-14 10 VA 48 V inductive 5000000 cycles AC-15 10 VA 110 V inductive 5000000 cycles AC-15 10 VA 220 V inductive 5000000 cycles AC-15 10 VA 48 V inductive 700000 cycles AC-12 50 VA 24 V resistive | |
| marking | 
				CE | |
| electrical connection | 
				Screw terminal block | |
| current consumption | 
				55 mA 5 V DC 70 mA 24 V DC rack | |
| module format | 
				Standard | |
| product weight | 
				0.33 kg | 
| dielectric strength | 
				2000 V 50/60 Hz 60 s | |
|---|---|---|
| standards | 
				73/23/EEC 89/336/EEC 92/31/EEC 93/68/EEC CSA C22.2 No 142 IEC 61131-2 UL 508 CSA C22.2 No 213 Class I Division 2 Group A CSA C22.2 No 213 Class I Division 2 Group B CSA C22.2 No 213 Class I Division 2 Group C CSA C22.2 No 213 Class I Division 2 Group D | |
| product certifications | 
				ABS BV DNV GL LR RINA RMRS | |
| ambient air temperature for operation | 
				0...60 °C | |
| ambient air temperature for storage | 
				-25...70 °C | |
| relative humidity | 
				10...95 % without condensation for operation 5...95 % without condensation for storage | |
| operating altitude | 
				0...2000 m | |
| protective treatment | 
				Conformal coating Humiseal 1A33 TC | |
| IP degree of protection | 
				IP20 | |
| pollution degree | 
				2 | 