Sidebar
Schneider ATSU01N232LT Soft starter for asynchronous motor
Viewed 1215 times
Product Description
Schneider ATSU01N232LT Soft starter for asynchronous motor - ATSU01 - 32 A - 200..480V - 7.5..15 KW
| range of product |
Altistart U01 and TeSys U
|
|
|---|---|---|
| product or component type |
Soft starter
|
|
| product destination |
Asynchronous motors
|
|
| product specific application |
Simple machine
|
|
| device short name |
ATSU01
|
|
| network number of phases |
3 phases
|
|
| [Us] rated supply voltage |
200...480 V - 10...10 %
|
|
| motor power kW |
15 kW 3 phases 400 V
7.5 kW 3 phases 230 V |
|
| motor power hp |
10 hp 3 phases 230 V
20 hp 3 phases 460 V |
|
| IcL starter rating |
32 A
|
|
| utilisation category |
AC-53B EN/IEC 60947-4-2
|
|
| current consumption |
100 mA
|
|
| type of start |
Start with voltage ramp
|
|
| power dissipation in W |
2.5 W at full load and at end of starting
322.5 W in transient state |
| assembly style |
With heat sink
|
|
|---|---|---|
| function available |
Integrated bypass
|
|
| supply voltage limits |
180...528 V
|
|
| supply frequency |
50...60 Hz - 5...5 %
|
|
| network frequency |
47.5...63 Hz
|
|
| output voltage |
<= power supply voltage
|
|
| [Uc] control circuit voltage |
24 V DC +/- 10 %
|
|
| starting time |
1 s 50
10 s 5 5 s 10 Adjustable from 1 to 10 s |
|
| deceleration time symb |
Adjustable from 1 to 10 s
|
|
| starting torque |
30...80 % of starting torque of motor connected directly on the
line supply
|
|
| discrete input type |
Logic LI1, LI2, BOOST stop, run and boost on start-up functions
<= 8 mA 27 kOhm
|
|
| discrete input voltage |
24...40 V
|
|
| input output isolation |
Galvanic between power and control
|
|
| discrete input logic |
Positive LI1, LI2, BOOST < 5 V and <= 0.2 mA > 13 V >= 0.5 mA
|
|
| discrete output current |
2 A DC-13
3 A AC-15 |
|
| discrete output type |
Open collector logic LO1 end of starting signal
Relay outputs R1A, R1C NO |
|
| discrete output voltage |
24 V 6...30 V open collector logic
|
|
| minimum switching current |
10 mA 6 V DC relay outputs
|
|
| maximum switching current |
2 A 30 V DC inductive cos phi = 0.5 20 ms relay outputs
2 A 250 V AC AC-15 inductive cos phi = 0.5 20 ms relay outputs |
|
| maximum switching voltage |
440 V relay outputs
|
|
| display type |
1 LED green starter powered up
1 LED yellow nominal voltage reached |
|
| tightening torque |
1.9...2.5 N.m
0.5 N.m |
|
| electrical connection |
4 mm screw clamp terminal rigid 1 1...10 mm² AWG 8 power circuit
Screw connector rigid 1 0.5...2.5 mm² AWG 14 control circuit 4 mm screw clamp terminal rigid 2 1...6 mm² AWG 10 power circuit Screw connector rigid 2 0.5...1 mm² AWG 17 control circuit Screw connector flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit 4 mm screw clamp terminal flexible without cable end 1 1.5...10 mm² AWG 8 power circuit Screw connector flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit 4 mm screw clamp terminal flexible with cable end 2 1...6 mm² AWG 10 power circuit 4 mm screw clamp terminal flexible without cable end 2 1.5...6 mm² AWG 10 power circuit Screw connector flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuit |
|
| marking |
CE
|
|
| operating position |
Vertical +/- 10 degree
|
|
| height |
314 mm
|
|
| width |
45 mm
|
|
| depth |
170 mm
|
|
| product weight |
0.49 kg
|
|
| Motor power range AC-3 |
7...11 kW at 200...240 V 3 phases
15...25 kW at 380...440 V 3 phases |
|
| motor starter type |
Soft starter
|
| electromagnetic compatibility |
Damped oscillating waves level 3 IEC 61000-4-12
Electrostatic discharge level 3 IEC 61000-4-2 Immunity to electrical transients level 4 IEC 61000-4-4 Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3 Voltage/current impulse level 3 IEC 61000-4-5 Conducted and radiated emissions level B CISPR 11 Conducted and radiated emissions level B IEC 60947-4-2 EMC immunity EN 50082-2 Harmonics IEC 1000-3-2 Harmonics IEC 1000-3-4 Conducted and radiated emissions level 3 IEC 61000-4-6 Immunity to conducted interference caused by radio-electrical fields IEC 61000-4-11 EMC immunity EN 50082-1 |
|
|---|---|---|
| standards |
EN/IEC 60947-4-2
|
|
| product certifications |
UL
C-Tick CSA CCC |
|
| IP degree of protection |
IP20
|
|
| pollution degree |
2 EN/IEC 60947-4-2
|
|
| vibration resistance |
1.5 mm peak to peak 3...13 Hz EN/IEC 60068-2-6
1 gn 13...150 Hz EN/IEC 60068-2-6 |
|
| shock resistance |
15 gn 11 ms EN/IEC 60068-2-27
|
|
| relative humidity |
5...95 % without condensation or dripping water EN/IEC 60068-2-3
|
|
| ambient air temperature for operation |
-10...40 °C without derating
40...50 °C with current derating of 2 % per °C |
|
| ambient air temperature for storage |
-25...70 °C EN/IEC 60947-4-2
|
|
| operating altitude |
<= 1000 m without derating
> 1000 m with current derating of 2.2 % per additional 100 m |

